Manual Pdf Fix: Sinotimer Svp-916

| Parameter | Description | Adjustable Range | Default Value | | :--- | :--- | :--- | :--- | | | Over-voltage Protection Value | 221V - 300V / OFF | 280V | | P02 | Over-voltage Recovery Value | 220V - 299V | 250V | | P03 | Over-voltage Action Delay Time | 0.1s - 10s | 0.1s | | P04 | Under-voltage Protection Value | 150V - 219V / OFF | 160V | | P05 | Under-voltage Recovery Value | 151V - 220V | 180V | | P06 | Under-voltage Action Delay Time | 0.1s - 10s | 0.1s | | P07 | Over-current Protection Value | 1A - 40A / 1A - 63A | 40A / 63A | | P08 | Over-current Action Delay Time | 0.1s - 512s | 5.0s | | P09 | Over-current Recovery Time | 2s - 512s | 2s / 60s | | P10 | Fault Recovery Delay Time | 2s - 255s | 2s | | P11 | Power-on Delay Time | 2s - 255s | 2s | | P12 | Reset Method Selection | HA = Auto / ノ = Manual | Auto (HA) | | P13 | Factory Reset | Press ▲ to reset | N/A |

If you want to view a more detailed explanation of the different types of Sinotimer protections, you can read the comprehensive Sinotimer SVP-912/916 Manual Overview on Scribd . Sinotimer Svp-916 Manual Pdf

The device features real-time digital monitoring for single-phase distribution boxes. : AC 230V, 50Hz/60Hz. | Parameter | Description | Adjustable Range |